Cavity drainage and ventilation in masonry cladding must:
Weep-holes alone are unsuitable for timber frame construction, and proprietary open perpends must be used.
Note: Proprietary open perpend inserts are available with insect screening incorporated. Their equivalent open area must be considered and installation centres reduced accordingly.
Where a cavity tray is proposed at DPC level, proprietary open perpends must be used above and below the cavity tray to provide:
Where flexible DPC materials are to be used as a cavity tray, they should have supporting evidence in the form of a Declaration of Performance to BS EN 14909:2012. They should also have third-party certification (BBA or similar UKAS accredited body) confirming their suitability for use as a cavity tray.
Care should be taken when specifying the use of a cavity tray at DPC level for timber framed properties to ensure adequate drainage and ventilation is given to the frame and sole plates.
Proprietary open perpends should be provided above and below the cavity tray and where flexible DPC materials are used as a cavity tray, they should have supporting evidence for their proposed use as highlighted in this article.